IDX hosting room uses Germany STULZ special precision cooling system to ensure the constant temperature and constant humidity of the hosting room. The working temperature is designed as: 22±2℃ in summer and 20±2℃ in winter with relative humidity remaining within 55±10%. |
All independent cooling areas are equipped with N+1 backup air-conditioner units to control the load balancing through online intelligent system.
|
Air-conditioner units adopt the under-floor air-distribution scheme and double compressor structure to guarantee the reliability of the operation. |
The cooling area is equipped with retaining wall and sewerage system; the cabinet area is installed with water leakage detector devices and all inlet valves are added with electronic control to thoroughly prevent any hidden risk of inlet to the hosting room. |
Computer room is designed with separate cool and hot air channels to greatly improve the cooling efficiency and energy utilization efficiency. |