SDS's IDX cooling system consists of central cooling system and special hosting room cooling system. For the security and stable operation of the computer system, the hosting room is equipped with redundancy air conditioner set with N+1 for each sealed fire prevention area. According to different functions, the custody hosting rooms on the 2nd floor, 3rd floor and 4th floor are equipped with special precision air conditioners of under-floor air-distribution. Besides, water-proof function is installed between air conditioner and cabinet area and the under-floor water proof function of the air conditioner is built as a slope with weep hole and the surrounding of cabinet area is equipped with water leakage detector with all inlet valves installed with electronic control valve.
Germany STULZ special precision air-conditioner to ensure the constant temperature and constant humidity of the hosting room as: 22±2℃ in summer and 20±2℃ in winter N+1 backup for all independent fire prevention areas; intelligent control system to control and the load balancing Double compressor and double-circuit power supply for each air conditioner Cooling capacity per square meter reaches 1KW~1.5KW
SDS IDX Cooling System
To facilitate the heat radiation of cabinet and based on the location of precision air conditioners in the hosting room and the principle of air circulation, cabinets every two lines are positioned face to face and the two neighboring lines of cabinets stand back to back. No outlet on the floor behind the cabinet. In this way, the hot air from the cabinet back will be absorbed by the air conditioner when it comes out since hot air rises upward and meanwhile the cold air from air conditioner, since it is relatively heavy, will be supplied to the cabinet through under-floor air distribution. This kind of air circulation helps to ensure that every cabinet stays within a relatively low temperature.
Outdoor Air System
2nd floor, 3rd floor and 4th floor adopt outdoor air system with 1500 m3/h air amount for each floor. Besides, each floor is installed with one outdoor air handler of constant temperature and constant humidity. The air amount is adjustable and outdoor air is distributed to the room through the original inlet. Air amount is 1500 m3/h with electrode humidification to keep the constant temperature and constant humidity of hosting room.
The 5th floor office area adopts fan-coil unit to conduct onsite control in order to meet the office requirement for comfortableness. Besides, offices take fan-coil unit + outdoor air system. Outdoor air handler: air amount 4000CMH, hoisted in the storage room, type: PAH20*2,cooling capacity: 43.6kw and heating capacity 48.6kw.
Natural Cooling with Outdoor Air
Refrigeration unit still needs to work to support the operation of equipment during transfer season and winter season since the equipment in power room produces much heat. In this case cooling process is undoubtedly energy consumptive. So the air-conditioning system of natural cooling with outdoor air is a better choice. Outdoor cold air is transferred into the room by air handler with its temperature and humidity treatment to meet the requirement for temperature and humidity without the running of the refrigeration unit.